The following table lists the power drops required for each number of SUs.
Table 10. Power-drop requirements
Number of SU nodes |
Required number of power drops |
||
Single phase |
Three-phase Delta |
Three-phase Wye |
|
Dense |
|||
4 |
2 |
1 |
1 |
8 |
3 |
1 |
1 |
12 |
4 |
2 |
1 |
16 |
5 |
3 |
2 |
Hybrid |
|||
4 |
2 |
2 |
2 |
8 |
4 |
2 |
2 |
12 |
6 |
2 |
2 |
16 |
8 |
2 |
2 |
All flash |
|||
4 |
2 |
2 |
2 |
8 |
4 |
2 |
2 |
12 |
4 |
2 |
2 |
16 |
6 |
2 |
2 |
The integrated system enables you to use different PDU connector types to best integrate into your data center, as listed in the following table.
Table 11. PDU and connector options
Location |
Single phase |
Three-phase Delta |
Three-phase Wye |
North America, Japan |
|
|
|
International |
IEC60309-332P6W |
Russellstoll 9P54U2T/1100 |
|
Australia |
Clipsal 56PA332 |
|
|